Welcome to the Pump Start Relay support section.
The PSR is fully compatible with all standard 24VAC controllers.
Section Menu
Mounting
Installation
-
Power Source Connection
IMPORTANT: Connecting the Pump Start Relay should only be done by a licensed electrician following local codes. Improper installation could result in shock or fire hazard
-
PSR-B
The PSR-B was developed to provide a solution for irrigation controller and pump start relays installations that have insufficient power to energize the pump relay. A common cause
-
REL 2
REL 2 is designed to enable multiple controllers to operate the same low-voltage device, such as a Master Valve or Pump Start Relay. This device must never be connected to high
Troubleshooting
Troubleshooting
-
Chattering
The chattering you hear on a pump start relay is usually caused by insufficient amperage arriving at the relay from the controller. The first question you should ask yourself is –